SCHOTT Home
SCHOTT North America
SCHOTT PYRAN® Platinum F
Fire- and Safety-Rated Glass-Ceramic


PRODUCT INFORMATION

Description

PYRAN® Platinum F is a fire-protection rated and impact- safety rated glazing material made from a transparent glass-ceramic with a thickness of 3/16" (5 mm). It has a surface applied 3M Scotchshield* Ultra Film and is intended for use in safety-rated locations such as door lites, transoms or sidelites, and windows with fire-rating requirements up to 90 minutes (up to 180 minutes in doors).



Features



  • Fire-rated up to 90 minutes (180 minutes in doors) with required hose stream test
  • Specially floated glass-ceramic with surface applied
    3M Scotchshield* Ultra Film
  • Transparent and wireless
  • Withstands thermal shock
  • Suited for use with standard fire-rated frames with the same rating
  • Conforms to positive pressure test standards
  • Environmentally-frinedly glass-ceramic; produced without the use of toxins
  • Can be used to construct insulated glazing units



General Characteristics



  • Thickness: 3/16" (5 mm)
  • Weight: 2.5 lbs/ft²
  • True color rendition
  • Surface finish: mirror-like
  • Maximum sheet sizes: Approximately 43" x 77"
  • Impact rating: ANSI Z97.1 and CPSC 16CFR1201 (Cat. I and II)



Listings

Rating
Location
Max. exposed area of glazing (in²)
Max. width of exposed glazing (in)
Max. height of exposed glazing (in)
Min. depth of grrove (in)
Up to 90 min Doors Non-Temp Rise
2,736 (19 ft²)
36
76
5/8
Up to 180 min Doors Temp Rise and Non-Temp Rise
100 (0.69 ft²)
12
33
1/2
Up to 90 min Other than Doors
3,422 (23.7 ft²)
76
76
5/8




Classified and labeled by Underwriters Laboratories, Inc. for the United States and Canada with File-No. R22036. All fire tests performed in accordance with UL 9, UL 10C, UBC 7-2 (1997), UBC 7-4 (1997), NFPA 257, NFPA 80, ASTM E2010-01, ASTM E2074-00, and ULC CAN4-S106.p>

Note: This product is not considered a barrier to radiant heat and has not met the ASTM E-119 or UL 263 test standards.

All listing information is subject to change. The current listing can be accessed in the UL directory under file #R22036 or upon request from SCHOTT.

For special component requirements, contact SCHOTT North America, Inc., 5530 Shepherdsville Road, Louisville, KY 40228 or phone (502) 657-4417.



Labeling

After cutting, each lite of PYRAN® Platinum F fire- and safety-rated glass-ceramic shall be permanently labeled according to code requirements with product and manufacturer’s name, mark from the authorized testing agency, fire rating, etc.



Storage & Handling

PYRAN® Platinum F fire- and safety-rated glass-ceramic should be handled with care during transportation, storage, inspection, and installation. It should be stored in dry conditions only and needs to be stacked upright or at a slight angle. In addition, the panels must be separated by an appropriate material, such as acid-free tissue paper, and the bottom edge must be supported along its entire length.



Installation

PYRAN® Platinum F shall only be installed into fire-rated frame and window assemblies carrying the same rating. Each PYRAN® Platinum F panel should be inspected carefully before installation, and any pieces with visible edge or surface damage should be sorted out. All glazing components and the stop height must be chosen according to the PYRAN® Platinum F UL classification. The panel must be placed on calcium silicate or hardwood setting blocks and glazed using PYRAN® Platinum F classified glazing tape, such as closed cell PVC, Fiberfrax tape or Pemko FG3000S90. The installation of the framed unit must comply with the frame supplier's instructions.

PYRAN® Platinum F is a specially developed glass-ceramic, that fulfills the fire protection rating requirements. The production process may create certain optical imperfections, such as bubbles or knots. Since these do not generally impair the transparency or the technical performance of the glass-ceramic, they do not represent cause for rejection or replacement.



Maintenance & Care

To maintain the aesthetics, it is important to keep the panel clean. A soft, clean, non-abrasive cloth and a mild soap, detergent, or non-abrasive window cleaning solution is suitable for cleaning. After cleaning, rinse immediately with clean water and remove any excess water from the panel surface. Also, do not allow any metal or hard parts of the cleaning equipment to come in contact with the panel surface.



pyran_platinum_f_data_sheets-final_12-07-09.pdf 2. PYRAN® Platinum F Data Sheets
spec_pyran_platinum_f-12-09.doc 2. PYRAN® Platinum F Specifications (in MS Word) - Section 08 81 00 in CSI MasterFormat
pyran_platinum_warranty.pdf PYRAN® Platinum Warranties
Contact

SCHOTT North America Inc.
Special Materials and Applications

5530 Shepherdsville Road
Louisville, KY 40228
USA
 +1-502-657-4413
 +1-502-966-4976
E-mail
More contacts
Trade Fairs & Events

05-12 to 05-14-2010

Construct 2010

Pennsylvania Convention Center, Philadelphia, PA

06-10 to 06-12-2010

AIA 2010

Miami, Florida

More trade fairs